Transformer Oil
Specialty Lubricants
Twin Specialties' line of transformer oils are recommended for use in grid and industrial transformers and electrical equipment components.
Unit of Measure
| Items |
/Asset/Shell_Drum.jpg 550026646 55 gal Shell Diala S2 ZX-A Transformer Oil |
/Asset/Shell_Tote.jpg 500005602 Bulk Shell Diala S2 ZX-A Transformer Oil |
/Asset/Shell_Drum.jpg 550068654 55 gal Shell Diala S4 ZX-IG Transformer Oil |
|||
| Quantity | N/A 55 gal | N/A 330 gal | N/A 55 gal | |||
| Viscosity at 40ºC | N/A 9 cSt | N/A 9 cSt | N/A 9.4 cSt | |||
| Viscosity at 100ºC | N/A 2.2 cSt | N/A 2.2 cSt | N/A 2.7 cSt | |||
| Flash Point | N/A 150 ºC | N/A 150 ºC | N/A 158 ºC | |||
| Pour Point | N/A -57 ºC | N/A -57 ºC | N/A -42 ºC | |||
| Aniline Point | N/A 69 ºC | N/A 69 ºC | N/A 114 ºC | |||
| Interfacial Tension at 25ºC | N/A 42 dynes/cm | N/A 42 dynes/cm | N/A 53 dynes/cm | |||
| Rotating Pressure Vessel Oxidation Test (RPVOT) | N/A 240 min | N/A 240 min | N/A 650 min | |||
| Dielectric Breakdown | N/A > 300 (Impulse) kV> 70 (After Treatment) kV40 (As Received) kV | N/A > 300 (Impulse) kV> 70 (After Treatment) kV40 (As Received) kV | N/A 36 kV | |||
| Dielectric Dissipation Factor | N/A 0.1 | N/A 0.1 | N/A 0.001 | |||
| Total Acid Number | N/A < 0.01 @ 72 hours mg KOH/g0.1 @ 164 hours mg KOH/g | N/A | N/A 0.02 mg KOH/g | |||
| 72 Hours Sludge by Mass | N/A < 0.01 % | N/A < 0.01 % | N/A 0.01 % | |||
| 164 Hours Sludge by Mass | N/A 0.01 % | |||||
| Gassing Tendency | N/A Complies | N/A Complies | N/A -5 | |||
| Oxidation Inhibitor Content | N/A Complies | N/A Complies | N/A 0.2% | |||
| PCB Content | N/A Not Detectable | |||||
| Water Content | N/A < 30 mg/kg | N/A < 30 mg/kg | N/A 7 mg/kg | |||
| Applications |
N/A
Transformers - Electrical insulating oil for grid and industrial transformers. Electrical Equipment - Components such as rectifiers, circuit breakers and switchgears. |
N/A
Transformers - Electrical insulating oil for grid and industrial transformers. Electrical Equipment - Components such as rectifiers, circuit breakers and switchgears. |
N/A
Power Plants Transformers |
|||
| Features and Benefits |
N/A
Extended Oil Life - Shell Diala S2 ZX-A is an inhibited oil giving outstanding oxidation performance and an extended oil life. System Efficiency - The good low temperature properties of the oil ensures proper heat transfer inside the transformer, even from low, starting temperatures. Transformer Protection - Shell Diala S2 ZX-A is non-corrosive towards copper, with no need for additional passivation. Shell Diala S2 ZX-A meets all relevant tests on copper corrosion ASTM D1275, and also the latest more severe tests: IEC 62535 and ASTM D1275B. |
N/A
Extended Oil Life - Shell Diala S2 ZX-A is an inhibited oil giving outstanding oxidation performance and an extended oil life. System Efficiency - The good low temperature properties of the oil ensures proper heat transfer inside the transformer, even from low, starting temperatures. Transformer Protection - Shell Diala S2 ZX-A is non-corrosive towards copper, with no need for additional passivation. Shell Diala S2 ZX-A meets all relevant tests on copper corrosion ASTM D1275, and also the latest more severe tests: IEC 62535 and ASTM D1275B. |
N/A
*Sulfur content below 1 ppm detection limit of ASTM D5185 |
|||
| Claims (Meets Requirements) | N/A ANSI/ASTM D3487 Type II | N/A ANSI/ASTM D3487 Type II | N/A ANSI/ASTM D3487 Type II IEC 60296 (Edition 4 year 2012); Table 2 Transformer Oil (I) (Inhibited Oil) Section 7.1 ("Higher Oxidation Stability & Low Sulfur Content") IEC 60296 (Edition 5 year 2020); Type A, Fully Inhibited High Grade Oils | |||
| Additional Information | N/A Storage Precautions - The critical electrical properties of Shell Diala S2 ZX-A are easily compromised by trace contamination with foreign material. Typically encountered contaminants include moisture, particles, fibers and surfacants. Therefore, it is imperative that electrical insulating oils be kept clean and dry. It is strongly recommended that storage containers be dedicated for electrical service and include airtight seals. It is further recommended that electrical insulating oils be stored indoors in climate-controlled environments. | N/A Storage Precautions - The critical electrical properties of Shell Diala S2 ZX-A are easily compromised by trace contamination with foreign material. Typically encountered contaminants include moisture, particles, fibers and surfacants. Therefore, it is imperative that electrical insulating oils be kept clean and dry. It is strongly recommended that storage containers be dedicated for electrical service and include airtight seals. It is further recommended that electrical insulating oils be stored indoors in climate-controlled environments. |
N/A
|
|||
| Power Factor at 25ºC | N/A | N/A | N/A 0.001 % | |||
| Power Factor at 100ºC | N/A | N/A | N/A 0.001 % | |||
|
|
||||||